  • Abstract
    Experiments at several source voltages have been carried out to clarify the influence of the voltage on various characteristics, such as arc duration, contact resistance and electrode mass change. In previous experiments, arc was generated only at break and at both make and break. In this report, arc is generated only at make. When only a make arc occurs, arc is generated by bounce of contacts. The source voltages are changed from DC100V to 160V, load current is set to 5A constant, and an electromagnetic contactor is operated continuously up to 100,000 times. As a result, the source voltage doesn´t influence average contact resistance and arc duration was very short. In addition, the crater was caused on the contact surface of the anode side. On the other hand, the pip was formed in the cathode side.
  • Keywords
    arcs (electric); cathodes; contactors; anode side; arc duration; cathode side; contact resistance; contact surface; electrode mass change; electromagnetic contactor; source voltage; voltage 100 V to 160 V; Anodes; Cathodes; Contact resistance; Electromagnetics; Surface resistance; Voltage measurement;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Contacts (Holm), 2012 IEEE 58th Holm Conference on
  • Conference_Location
    Portland, OR
  • ISSN
    1062-6808
  • Print_ISBN
    978-1-4673-0778-9
  • Type

    conf

  • DOI
    10.1109/HOLM.2012.6336583
  • Filename
    6336583