DocumentCode :
1905907
Title :
Harmonics study for three-phase transformer under DC inrushing
Author :
Xiaoping, Li ; Xishan, Wen ; Lei, Lan ; Yadong, Fan
Author_Institution :
Sch. of Electr. Eng., Wuhan Univ.
fYear :
2006
fDate :
Feb. 27 2006-March 3 2006
Firstpage :
227
Lastpage :
230
Abstract :
In this paper, the circuit model of three-phase transformer with three-legs under DC inrushing is set up. Considering the magnetic coupling of three legs, the nonlinear single-value curve of one leg of transformer is deduced. Combining the circuit equation and nonlinear B ~ H curve of one leg of transformer, we gain the wave and harmonics distribution of exciting current. Because of magnetic coupling among three legs, although the winding of transformer have DC current, DC flux doesn´t exist in the legs of three-phase transformer. So the DC current inrushes the winding of symmetric have little influence on the exciting current, but increase heat loss
Keywords :
harmonic analysis; matrix algebra; power transformers; DC flux; DC inrushing; circuit model; harmonics distribution; harmonics study; magnetic coupling; nonlinear single-value curve; three-phase transformer; Circuit faults; Leg; Magnetic flux; Phase transformers; Power supplies; Resistors; Saturation magnetization; Surges; Tellurium; Transformer cores; three-phase transformer with three legs Harmonic;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electromagnetic Compatibility, 2006. EMC-Zurich 2006. 17th International Zurich Symposium on
Conference_Location :
Singapore
Print_ISBN :
3-9522990-3-0
Type :
conf
DOI :
10.1109/EMCZUR.2006.214911
Filename :
1629601
Link To Document :