• DocumentCode
    190758
  • Title

    Changes in cascading failure risk with generator dispatch method and system load level

  • Author

    Rezaei, Pooya ; Hines, Paul D.H.

  • Author_Institution
    School of Engineering, University of Vermont, Burlington, VT
  • fYear
    2014
  • fDate
    14-17 April 2014
  • Firstpage
    1
  • Lastpage
    5
  • Abstract
    Industry reliability rules increasingly require utilities to study and mitigate cascading failure risk in their system. Motivated by this, this paper describes how cascading failure risk, in terms of expected blackout size, varies with power system load level and pre-contingency dispatch. We used Monte Carlo sampling of random branch outages to generate contingencies, and a model of cascading failure to estimate blackout sizes. The risk associated with different blackout sizes was separately estimated in order to separate small, medium, and large blackout risk. Results from N − 1 secure models of the IEEE RTS case and a 2383 bus case indicate that blackout risk does not always increase with load level monotonically, particularly for large blackout risk. The results also show that risk is highly dependent on the method used for generator dispatch. Minimum cost methods of dispatch can result in larger long distance power transfers, which can increase cascading failure risk.
  • Keywords
    Cascading failure risk; Monte Carlo simulation; security-constrained optimal power flow;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    T&D Conference and Exposition, 2014 IEEE PES
  • Conference_Location
    Chicago, IL, USA
  • Type

    conf

  • DOI
    10.1109/TDC.2014.6863470
  • Filename
    6863470