Title :
Electrical strength of distribution insulators under steep front, short duration pulse
Author :
Grzybowski, S. ; Kappenman, J. ; Radasky, W.A.
Author_Institution :
Mississippi State Univ., MS
fDate :
Feb. 27 2006-March 3 2006
Abstract :
The CFO voltage and V-t characteristic of 15 kV power distribution insulators are important factors in insulation coordination design of power distribution systems. Insulation designs for distribution feeders are usually based on 1.2/50 mus lightning impulse, while insulator behavior under steep front short duration (SFSD) pulses is not concerned. The generated SFSD impulse in this study has a 60 ns front and less than 200 ns of the tail. The insulators are evaluated under dry and wet condition with both negative and positive polarity impulses
Keywords :
insulators; lightning protection; power distribution protection; 1.2 mus; 15 kV; 50 mus; CFO voltage; distribution insulators; electrical strength; lightning impulse; power distribution insulators; power distribution systems; steep front short duration; Dielectrics and electrical insulation; Flashover; Insulator testing; Lightning; Plastic insulation; Polymers; Power distribution; Tail; USA Councils; Voltage; Distribution insulators; critical flashover voltage (CFO); lightning impulse; steep front short duration pulse; wood crossarm;
Conference_Titel :
Electromagnetic Compatibility, 2006. EMC-Zurich 2006. 17th International Zurich Symposium on
Conference_Location :
Singapore
Print_ISBN :
3-9522990-3-0
DOI :
10.1109/EMCZUR.2006.215008