DocumentCode
1912031
Title
Transient calculation of internal faults in the salient-pole synchronous machine and research on their main equipment protection schemes
Author
Xiangheng, Wang ; Bei, Ouyang ; Yuguang, Sun ; Weijian, Wang
Author_Institution
Dept. of Electr. Eng., Tsinghua Univ., Beijing, China
fYear
2001
fDate
37012
Firstpage
133
Lastpage
139
Abstract
Based on the multi-loop method, a mathematical model for the salient-pole synchronous machine is established. The transient and steady-state behavior of the machine with internal faults is simulated through the model, and it is conformable with the experiment result. According to the simulation results, the sensitivities of different protection schemes are calculated under some typical kinds of internal faults. It is found that the transient sensitivity is higher than the corresponding steady-state sensitivity under the same condition
Keywords
machine protection; machine theory; synchronous machines; transient analysis; 12 kW; completed longitudinal differential protection; internal faults; mathematical model; multi-loop method; noncompleted longitudinal differential protection; protection sensitivity; salient-pole synchronous machine; single element transverse differential protection; split transverse differential protection; stator windings; steady-state behavior; steady-state sensitivity; transient behavior; transient calculation; transient sensitivity; Circuit faults; Couplings; Electric machines; Equations; Mathematical model; Protection; Stators; Steady-state; Synchronous machines; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Industrial and Commercial Power Systems Technical Conference, 2001. Conference Record. Papers Presented at the 2001 Annual Meeting. 2001 IEEE
Conference_Location
New Orleans, LA
Print_ISBN
0-7803-7055-4
Type
conf
DOI
10.1109/ICPS.2001.966523
Filename
966523
Link To Document