DocumentCode :
1912892
Title :
Voltage collapse and its avoidance
Author :
Hawkin, Nigel T.
fYear :
1997
fDate :
35544
Firstpage :
42401
Lastpage :
42406
Abstract :
This paper discusses the phenomenon which leads to voltage collapse. It describes how automatic control equipment may exacerbate the decay of system voltage levels, with specific reference to the automatic tap changing of supply transformers. It addresses the factors which affect the onset of such behaviour, and operational requirements for the avoidance of voltage collapse. Reference is made to on-line algorithms which could be used to provide advice to power system control engineers which would help them avoid voltage collapse by making the most effective use of reactive resources
fLanguage :
English
Publisher :
iet
Conference_Titel :
Voltage Collapse (Digest No: 1997/101), IEE Colloquium on
Conference_Location :
London
Type :
conf
DOI :
10.1049/ic:19970563
Filename :
664640
Link To Document :
بازگشت