Title :
Bad data analysis using the composed measurements errors for power system state estimation
Author :
Bretas, N.G. ; Bretas, A.S.
Author_Institution :
Electr. Eng. Dept., Univ. of Sao Paulo, Sao Paulo, Brazil
Abstract :
In this paper, a topological/geometrical based approach is used to define the undetectability index (UI), which provides the position of a measurement related to the range space of the Jacobean matrix of the power system. The higher the value of this index, for a measurement, the closer it will be to the range space of that matrix, that is, the error in measurements with high UI is not reflected in their residuals, thus masking a possible gross error those measurements might have. Using the UI of a measurement, the possible gross error the state estimation process might mask is recovered; then the total gross error of that measurement is composed and used to the gross error detection and identification test. The gross error processing turns out to be very simple to implement, requiring only a few adaptations to the existing state estimation software. The IEEE-14 bus system is used to validate the proposed gross error detection and identification test.
Keywords :
Jacobian matrices; measurement errors; power system measurement; power system state estimation; IEEE-14 bus system; Jacobean matrix; bad data analysis; composed measurement errors; gross error detection; gross error identification; power system state estimation; undetectability index; Indexes; Measurement errors; Measurement uncertainty; Pollution measurement; Power measurement; Power systems; State estimation; Gross Errors Analysis; Orthogonal Projections; Recovering Errors; State Estimation; Undetectability Index;
Conference_Titel :
Bulk Power System Dynamics and Control (iREP) - VIII (iREP), 2010 iREP Symposium
Conference_Location :
Rio de Janeiro
Print_ISBN :
978-1-4244-7466-0
Electronic_ISBN :
978-1-4244-7465-3
DOI :
10.1109/IREP.2010.5563279