• DocumentCode
    1929171
  • Title

    Analysis on capability of harmonic damping using active filter acting as resistive harmonic impedance

  • Author

    Hasan, K.N.M. ; Luna, Alvaro ; Candela, J. Ignacio ; Rodriguez, Paul

  • Author_Institution
    Tech. Univ. of Catalonia, Terrassa, Spain
  • fYear
    2013
  • fDate
    15-19 Sept. 2013
  • Firstpage
    2928
  • Lastpage
    2933
  • Abstract
    This paper presents the analysis of shunt active filter (SAF) in harmonic damping. SAF with voltage-based detection control act as an active damping and able to attenuate harmonic propagation throughout the power distribution network. The active filter is implemented on two different power line networks to assess its practicality in different network configuration. The first network is 220-V distribution power line and the second network is the reduced equivalent WPP network of 150-kV, 444.4-MVA. Assessment on the best place for active filter implementation is supported by using harmonic resonance mode analysis method.
  • Keywords
    active filters; damping; power conversion harmonics; power distribution lines; power harmonic filters; WPP network; apparent power 444.4 MVA; distribution power line networks; harmonic damping capability analysis; harmonic propagation attenuation; harmonic resonance mode analysis method; network configuration; resistive harmonic impedance; shunt active filter; voltage 150 kV; voltage 220 V; voltage-based detection control act; Active filters; Damping; Harmonic analysis; Impedance; Passive filters; Power harmonic filters; Resonant frequency;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Energy Conversion Congress and Exposition (ECCE), 2013 IEEE
  • Conference_Location
    Denver, CO
  • Type

    conf

  • DOI
    10.1109/ECCE.2013.6647082
  • Filename
    6647082