    Selection of setpoint for the degraded voltage relays at commercial nuclear power plants

  • Author

    Das, Ranjit K. ; Julka, Anil

  • Author_Institution
    Asta Engineering, Inc., Malvern, PA, USA
  • fYear
    1992
  • fDate
    25-31 Oct 1992
  • Firstpage
    775
  • Abstract
    Inappropriate setting of the degraded voltage relays at commercial nuclear power plants has subjected the class 1E loads to voltages below their operating range and caused spurious actuation of the undervoltage protection scheme as indicated in the referenced information notices. The authors present a methodology that can be successfully used to eliminate such concerns. A similar method has been used at Nine Mile Point Unit 2 (NMP2). This methodology is generic and can be effectively used in other nuclear power plants. Historically, electrical protection schemes do not use tolerances in accordance with the guidelines provided in Regulatory Guide 1.105. It is noted that application of these guidelines for selection of the degraded voltage relay setpoint and reset value will ensure adequate voltages for all class 1E loads and eliminate nuisance tripping
  • Keywords
    nuclear power stations; power system protection; relays; Nine Mile Point Unit 2; actuation; class 1E loads; degraded voltage relays; nuclear power plants; nuisance tripping; setpoint; undervoltage protection; Acceleration; Degradation; Delay effects; Instruments; Low voltage; Power generation; Power system protection; Protective relaying; Relays; Safety;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Nuclear Science Symposium and Medical Imaging Conference, 1992., Conference Record of the 1992 IEEE
  • Conference_Location
    Orlando, FL
  • Print_ISBN
    0-7803-0884-0
  • Type

    conf

  • DOI
    10.1109/NSSMIC.1992.301420
  • Filename
    301420