• DocumentCode
    1935080
  • Title

    Voltage sag and unbalance generator for power quality testing of adjustable speed drives

  • Author

    Tallam, Rangarajan M. ; Lukaszewski, Richard A.

  • Author_Institution
    Drives Bus., Rockwell Autom., Mequon, WI, USA
  • fYear
    2013
  • fDate
    15-19 Sept. 2013
  • Firstpage
    4565
  • Lastpage
    4571
  • Abstract
    Adjustable speed drives (ASDs) experience several power quality events occurring on the AC line - the most common are voltage sags and interruptions, and voltage unbalance. ASD manufacturers test the immunity of AC drives to voltage sags, to conform to the requirements of SEMI F47-0706 and IEC 61000-4-34 standards. Immunity to voltage unbalance is required to conform to the IEC 61800-3 standard. In this paper, voltage sag and unbalance generator topologies are derived from previously proposed voltage sag correctors. Control methods are also proposed for the new topologies, for applications to ASD power quality immunity testing.
  • Keywords
    IEC standards; power supply quality; variable speed drives; AC line; ASD power quality immunity testing; IEC 61000-4-34 standard; IEC 61800-3 standard; SEMI F47-0706 standard; adjustable speed drives; voltage interruptions; voltage sags; voltage unbalance generator; Generators; IEC standards; Power quality; Rectifiers; Topology; Variable speed drives; Voltage fluctuations;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Energy Conversion Congress and Exposition (ECCE), 2013 IEEE
  • Conference_Location
    Denver, CO
  • Type

    conf

  • DOI
    10.1109/ECCE.2013.6647312
  • Filename