Analytical investigation of the effect of wind farm equipped with SCIG on voltage stability
Author :
Dahraie, M. Vahedipour ; Najafi, H.R. ; Ebadian, M.
Author_Institution :
Fac. of Electr. & Comput. Eng., Univ. of Birjand, Birjand, Iran
fYear :
2012
fDate :
6-8 March 2012
Firstpage :
121
Lastpage :
126
Abstract :
In this paper, the effect of wind farm equipped with SCIG on the static voltage stability of the power system is investigated analytically. To achieve this objective, the active and reactive output power of wind farm has been obtained at wind speed and generator terminal voltage. By using an appropriate model for SCIG and by linking the wind farm to a simple two-bus power system, the bus load voltage has been calculated. By calculating deflection point at different wind speeds, the maximum loading curve of the system at wind speed is obtained. This curve shows the stable and unstable regions of the system at different wind speeds. In order to obtain an appropriate criterion for the effect of wind farm on the static voltage stability, a new index has been introduced and by using it the effect of wind farm on static voltage stability is investigated.
Keywords :
asynchronous generators; power system stability; wind power plants; SCIG; active output power; bus load voltage; maximum loading curve; reactive output power; simple two-bus power system stability; static voltage stability; wind farm; wind generator terminal voltage; wind speed; Indexes; Power system stability; Reactive power; Stability criteria; Wind farms; Wind speed; squirrel cage induction generator (SCIG); static voltage stability; voltage stability; wind farm;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Renewable Energy and Distributed Generation (ICREDG), 2012 Second Iranian Conference on
Conference_Location :
Tehran
Print_ISBN :
978-1-4673-0663-8
Electronic_ISBN :
978-1-4673-0664-5
Type :
conf
DOI :
10.1109/ICREDG.2012.6190446
Filename :
6190446
Link To Document :
بازگشت