• DocumentCode
    1941107
  • Title

    Quadrilateral relay based distance protection scheme for transmission lines under varying system conditions

  • Author

    Aneesh, S. ; Angel, T.S.

  • Author_Institution
    Dept. of Electr. & Electron. Eng., Amrita Vishwa Vidyapeetham, Kollam, India
  • fYear
    2015
  • fDate
    24-26 June 2015
  • Firstpage
    35
  • Lastpage
    39
  • Abstract
    Quadrilateral relay provides flexible protection during high fault resistance of ground and phase faults. This is advantageous for protection of phase-to-earth faults on short lines, non-effectively earthed systems and feeders with extremely high tower footing resistance. It also provides fault impedance coverage for both phase to phase and phase to ground faults. The proposed work intends the development of a numerical quadrilateral distance relay that can retain its function even under a major change in system configuration. The proposed relaying scheme is analyzed by coding the relay logic and simulating the system with transmission network in MATLAB/Simulink. Different factors influencing the performance of quadrilateral relay are studied and verified. It is observed that the scheme is adaptive to the system variations and mal trips are reduced.
  • Keywords
    power transmission faults; power transmission protection; relay protection; fault impedance coverage; ground faults; high fault resistance; numerical quadrilateral distance relay; phase faults; phase to ground faults; phase to phase faults; phase-to-earth faults; quadrilateral relay based distance protection scheme; relay logic; transmission lines; transmission network; varying system conditions; Adaptive systems; Impedance; Mathematical model; Protective relaying; Resistance; Software packages; Distance relaying; adaptive protection; fault resistance; quadrilateral relays; relay mal operation;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Advancements in Power and Energy (TAP Energy), 2015 International Conference on
  • Conference_Location
    Kollam
  • Type

    conf

  • DOI
    10.1109/TAPENERGY.2015.7229589
  • Filename
    7229589