DocumentCode :
1942521
Title :
Measurement of grounding resistance by triangular grid in Brunei Darussalam
Author :
Salam, M.A. ; Jaafar, Salinah ; Izhermi, M.
Author_Institution :
Dept. of Electr. & Electron. Eng., Inst. Technol. Brunei, Jalan Tungku, Brunei
fYear :
2011
fDate :
28-30 Sept. 2011
Firstpage :
1
Lastpage :
3
Abstract :
In this paper, the fall-of-potential (three-pole) method is used to measure grounding resistance by using triangular grid under dry and wet conditions. The grounding resistances are found to be 8.4Ω, and 8.2Ωrespectively for dry and wet conditions at 1.8 m length of buried electrode with pure copper rod. The linear regression analysis is used to establish the empirical relationship between grounding resistance and length of buried triangular grid.
Keywords :
earthing; electric resistance measurement; electrodes; power grids; regression analysis; Brunei Darussalam; buried triangular grid electrode; dry condition; fall-of-potential method; grounding resistance measurement; linear regression analysis; resistance 8.2 ohm; resistance 8.4 ohm; size 1.8 m; wet condition; Triangular grid; fall-of-potential method; grounding resistance; regression analysis;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Utility Exhibition on Power and Energy Systems: Issues & Prospects for Asia (ICUE), 2011 International Conference and
Conference_Location :
Pattaya City
Print_ISBN :
978-1-4673-6006-7
Type :
conf
DOI :
10.1109/ICUEPES.2011.6497745
Filename :
6497745