Title :
Minimization of impact from electric vehicle supply equipment to the electric grid using a dynamically controlled battery bank for peak load shaving
Author :
Tesfaye, M. ; Castello, C.C.
Author_Institution :
Tennessee State Univ., Nashville, TN, USA
Abstract :
This research presents a comparison of two control systems for peak load shaving using local solar power generation (i.e., photovoitaic array) and local energy storage (i.e., battery bank). The purpose is to minimize load demand of electric vehicle supply equipment (EVSE) on the electric grid. Static and dynamic control systems are compared to decrease demand from EVSE. Static control of the battery bank is based on charging and discharging to the electric grid at fixed times. Dynamic control, with 15-minute resolution, forecasts EVSE load based on data analysis of collected data. In the proposed dynamic control system, the sigmoid function is used to shave peak loads while limiting scenarios that can quickly drain the battery bank. These control systems are applied to Oak Ridge National Laboratory´s (ORNL) solar-assisted electric vehicle (EV) charging stations. This installation is composed of three independently grid-tied sub-systems: (1) 25 EVSE; (2) a 47 kW photovoitaic (PV) array; and (3) a 60 kWh battery bank. The dynamic control system achieved the greatest peak load shaving, up to 34% on a cloudy day and 38% on a sunny day. The static control system was not ideal; peak load shaving was 14.6% on a cloudy day and 12.7% on a sunny day. Simulations based on ORNL data show solar-assisted EV charging stations combined with the proposed dynamic battery control system can negate up to 89% of EVSE load demand on sunny days.
Keywords :
battery powered vehicles; battery storage plants; photovoltaic power systems; power generation control; power grids; secondary cells; solar cell arrays; EVSE; ORNL data; ORNL solar-assisted EV charging stations; Oak Ridge National Laboratory solar-assisted electric vehicle charging stations; PV array; battery bank static control system; dynamic battery control system; dynamically controlled battery bank; electric grid; electric vehicle supply equipment; independently grid-tied subsystems; load demand minimization; local energy storage; local solar power generation; peak load shaving; photovoltaic array; power 47 kW; sigmoid function; time 15 min; Arrays; Batteries; Control systems; Discharges (electric); Electric vehicles; System-on-chip; Vehicle dynamics; Battery Management Systems; Control System; Electric Vehicles; Power System Control; Scheduling Algorithm;
Conference_Titel :
Innovative Smart Grid Technologies (ISGT), 2013 IEEE PES
Conference_Location :
Washington, DC
Print_ISBN :
978-1-4673-4894-2
Electronic_ISBN :
978-1-4673-4895-9
DOI :
10.1109/ISGT.2013.6497815