Title :
AGC of a hydrothermal system with thyristor controlled phase shifter in the tie-line
Author :
Abraham, Rajesh Joseph ; Das, D. ; Patra, Amit
Author_Institution :
Dept. of Electr. Eng., Indian Inst. of Technol., Kharagpur
Abstract :
This paper presents the analysis of automatic generation control (AGC) of a two-area interconnected hydrothermal system considering a thyristor controlled phase shifter (TCPS) in series with the tie-line. It is possible to stabilize the system frequency and tie-power oscillations by controlling the phase angle of TCPS which is expected to provide a new ancillary service for the future power systems. A control strategy using TCPS is proposed to provide active control of system frequency. Gain settings of the integral controllers without and with TCPS are optimized using integral squared error (ISE) technique following a step load disturbance in either of the areas by minimizing a quadratic performance index. Analysis reveals that a TCPS is quite capable of suppressing the frequency and tie-power oscillations effectively under the occurrence of sudden load changes in any of the areas as compared to that obtained without TCPS
Keywords :
frequency control; hydrothermal power systems; oscillations; phase shifters; power generation control; power system interconnection; thyristors; AGC; automatic generation control; frequency control; integral squared error technique; interconnected hydrothermal system; load disturbance; phase angle control; quadratic performance index; thyristor controlled phase shifter; tie-power oscillation; Automatic control; Automatic generation control; Control systems; Error correction; Frequency; Performance gain; Phase shifters; Power system analysis computing; Power system interconnection; Thyristors;
Conference_Titel :
Power India Conference, 2006 IEEE
Conference_Location :
New Delhi
Print_ISBN :
0-7803-9525-5
DOI :
10.1109/POWERI.2006.1632529