• DocumentCode
    1961793
  • Title

    Transmission line tower collapse investigation: A case study

  • Author

    Bothma, J.G.

  • Author_Institution
    Parsons Brinckerhoff, Johannesburg, South Africa
  • fYear
    2012
  • fDate
    9-13 July 2012
  • Firstpage
    1
  • Lastpage
    8
  • Abstract
    Two adjacent 110kV self support suspension towers failed under broken conductor conditions. The conductor failed due to lightning damage and fatigue contributed to by Aeolian vibration. There were no earth wires on the structures which could prevent lightning damage and subsequent conductor breakage. The earth wires have a structural benefit of preventing a potential tower failure in excessive twisting of the tower top during broken phase conductor loading. This paper presents a methodology for the tower failure investigation using finite element modeling. The loading used under broken conductor conditions and the slenderness of members will be discussed. Recommendations for remedial strategies will be made.
  • Keywords
    conductors (electric); fatigue; finite element analysis; fracture; lightning protection; poles and towers; power transmission lines; Aeolian vibration; broken conductor conditions; conductor breakage; earth wires; fatigue; finite element modeling; lightning damage prevention; phase conductor loading; potential tower failure; remedial strategies; self support suspension towers; transmission line tower collapse investigation; voltage 110 kV; Broken conductor conditions; Failure sequencing; Finite Element Analysis; Impact Loading; Residual Static Loading; Security Loading; Suspension tower collapse;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Engineering Society Conference and Exposition in Africa (PowerAfrica), 2012 IEEE
  • Conference_Location
    Johannesburg
  • Print_ISBN
    978-1-4673-2548-6
  • Type

    conf

  • DOI
    10.1109/PowerAfrica.2012.6498616
  • Filename
    6498616