• DocumentCode
    1964647
  • Title

    Design of a New Integrated Real Time Device to Monitor Power Harmonic Pollution

  • Author

    Tingfang, Yang ; Ting, T.O.

  • Author_Institution
    Sch. of Electr. & Inf. Eng., Changsha Univ. of Sci. & Technol., Changsha
  • Volume
    4
  • fYear
    2008
  • fDate
    12-14 Dec. 2008
  • Firstpage
    182
  • Lastpage
    185
  • Abstract
    A new integrated device is put forward to monitor harmonic pollution. This system takes a 8-bit microcontroller MPC860 chip, a PowerPC TM real time system controller that produced by Motorola´s company as the nucleus and is composed of multi-channels data synchronous acquisition system in the Capacitor Voltage Transformer (CVT), which can suppress the ferromagnetic resonance, satisfy the long-range monitor and show a good frequency response. The harmonic analysis algorithm adopts Fast Fourier Transform (FFT). The measured quantities are analysed and compared with international standards. This new compact system has resolved problems of traditional models with inefficient performance and complicated program. It also can communicate with monitor center through telephone line, serial port and wireless, etc. This new device is carried out in order to identify the sources of harmonics generation, estimate the level of distortion and monitor electric power signal variations very efficiently. Simulation results show the new device helps to facilitate the supervision of electric power signals and many kinds of electric power quality disturbances and harmonic pollution are tested thoroughly.
  • Keywords
    data acquisition; fast Fourier transforms; microprocessor chips; potential transformers; power supply quality; power system harmonics; power system measurement; 8-bit microcontroller MPC860 chip; PowerPC TM real time system controller; capacitor voltage transformer; electric power quality disturbances; electric power signals; fast Fourier transform; ferromagnetic resonance suppression; harmonic analysis algorithm; harmonics generation; integrated real time device; multichannels data synchronous acquisition system; power harmonic pollution; Capacitors; Control systems; Magnetic resonance; Microcontrollers; Monitoring; Pollution; Power system harmonics; Real time systems; Voltage control; Voltage transformers; CVT; Monitor harmonic pollution; real time;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Computer Science and Software Engineering, 2008 International Conference on
  • Conference_Location
    Wuhan, Hubei
  • Print_ISBN
    978-0-7695-3336-0
  • Type

    conf

  • DOI
    10.1109/CSSE.2008.718
  • Filename
    4722593