DocumentCode
1972666
Title
The identification of transient fault in series compensated line
Author
Zhang, Yan ; Shang, Liqun
Author_Institution
Xi´´an Univ. of Sci. & Technol., Xi´´an, China
fYear
2011
fDate
16-18 Sept. 2011
Firstpage
5094
Lastpage
5098
Abstract
This paper mainly analyzes the transmission line which is in series with compensation capacitor. For the compensation transmission line will contain rich transient components from low to high frequency when it occurs one phase ground fault. In this paper, we use the low-frequency resonance which generated by series capacitor and shunt inductor to determine the nature of the fault. First, the voltage will be filtered, extracts the low frequency components and integral it to calculating the low-frequency energy. Comparing the energy of arc to determine the nature of the fault, and then to judge whether bypass the series capacitor in order to prepare for recloure.
Keywords
compensation; earthing; fault location; inductors; power capacitors; power system transients; power transmission faults; power transmission lines; compensation capacitor; low frequency component extraction; low-frequency resonance; one phase ground fault; series capacitor; series compensated line; shunt inductor; transient fault identification; transmission line; Capacitors; Circuit faults; Power system stability; Power transmission lines; Switches; Transient analysis; MATLAB; automatic reclosure; low-frequency components; series compensation;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical and Control Engineering (ICECE), 2011 International Conference on
Conference_Location
Yichang
Print_ISBN
978-1-4244-8162-0
Type
conf
DOI
10.1109/ICECENG.2011.6057013
Filename
6057013
Link To Document