Title :
Some operating experiences of 10kV small signal EVT in Fengzhou digital substation
Author :
Huang, Shangyuan ; Chen, Jinmu ; Zhang, Jinsong
Author_Institution :
Jiading Power Co., Shanghai Municipal Electr. Power Co., Shanghai, China
Abstract :
The principle, structure and output signal of an electronic voltage instrument transformer based on a resistive voltage divider are different with that of a traditional voltage transformer, so the stability and reliability should be tested and improved during the practical run this paper classifies the problem of the electronic voltage instrument transformer and analyses them that is based on the operation data of the 10 kV electronic voltage transformer in Fengzhou digital substation. The analysis results show that the main body runs well, but the signal could be affected by the accessories (power signal distributor signal transmission cable). So in the end the article gives some suggestions that the problem could by settled by improving the production design and the maintenance.
Keywords :
potential transformers; substations; voltage dividers; Fengzhou digital substation; electronic voltage instrument transformer; maintenance; production design; resistive voltage divider; small signal EVT; voltage 10 kV; Cable shielding; Electromagnetic compatibility; Instrument transformers; Reliability; Substations; Voltage measurement; 10kV EVT; EMC; Faults; Recommendation; Resisitor Divider; Signal Cable;