• DocumentCode
    1975028
  • Title

    Effect of arc time on the current breaking capability of vacuum interrupters

  • Author

    Taylor, E.D. ; Lawall, A. ; Genzmer, J. ; Heydenreich, T.

  • Author_Institution
    Siemens AG, Berlin, Germany
  • fYear
    2013
  • fDate
    20-23 Oct. 2013
  • Firstpage
    1
  • Lastpage
    4
  • Abstract
    Vacuum interrupters on medium voltage power systems need to interrupt short-circuit currents over a wide range of arc times. Synthetic testing allows the careful study of the interruption performance over arc times ranging from 0 to 13.3ms for a 50Hz system. Comparing the interruption performance as a function of arc time observed in single- and three-phase direct testing and single-phase synthetic testing gives good agreement. This agreement extends over different rating points, different contact designs, and different arc control methods. Additional tests compared synthetic tests with and without re-ignition for arc times greater than 10ms.
  • Keywords
    arcs (electric); electric ignition; power systems; short-circuit currents; vacuum interrupters; arc time effect; current breaking capability; frequency 50 Hz; medium voltage power system; short-circuit current interruption; single-phase direct testing; single-phase synthetic testing; three-phase direct testing; time 0 ms to 13.3 ms; vacuum interrupter; Interrupters; Presses; Switches; Time-frequency analysis; Vacuum arcs;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electric Power Equipment - Switching Technology (ICEPE-ST), 2013 2nd International Conference on
  • Conference_Location
    Matsue
  • Type

    conf

  • DOI
    10.1109/ICEPE-ST.2013.6804288
  • Filename
    6804288