Study on structures to support AMF electrodes and compensate for AMF loss by itself
Author :
Hyeong Goo Lee ; Jong Sung Kang ; Chul Hyun Ahn ; Byungsan Baek ; Man Gyu Cho
Author_Institution :
Hyundai Heavy Ind. Co., Ltd., Yongin, South Korea
fYear :
2013
fDate :
20-23 Oct. 2013
Firstpage :
1
Lastpage :
4
Abstract :
The AMF (Axial Magnetic Field) electrodes of VI (vacuum interrupters) can be largely classified into two groups; coil type and cup type. While TMF (Transverse Magnetic Field) electrodes do not need structures to support the electrodes, the AMF electrodes should have them inside. In case of separating welded contacts, it is recommended that the structures be brazed with electrodes and contacts. In this case although these structures are generally made of metal of which conductivity is low e.g. stainless steel, the current flows partly through them, which prevents AMF from generating.
Keywords :
electrodes; magnetic fields; stainless steel; vacuum interrupters; AMF electrodes; AMF loss; TMF electrodes; axial magnetic field electrodes; current 50 kA; stainless steel; transverse magnetic field electrodes; vacuum interrupters; Contacts; Electrodes; Integrated circuit modeling; Interrupters; Magnetic fields; Steel; Welding;