Title :
Research about influence of contact burning loss on dielectric recovery characteristic for SF6 circuit breaker
Author :
Xintao Li ; Xin Lin ; Jianyuan Xu ; Feiming Wang ; Yutian Zhou
Author_Institution :
Sch. of Electr. Eng., Shenyang Univ. of Technol., Shenyang, China
Abstract :
When circuit breaker repeatedly breaks small capacitive current of compensation equipments,serious burning loss phenomenon is placed on the surface of static arc contact, which will lead to changing of contact shape. It may finally result in electric field distortion and adversely affect dielectric recovery characteristic. The mathematical models of electric field and flow field have been established in 126 kV SF6 circuit breaker. According to gas breakdown criterion of the streamer theory, dielectric recovery characteristic curves in the condition of burning loss angle θ=60° and no-burning loss have been researched. Then electric field distributions in various burning loss angles have been calculated. Results illustrate that seriously impacts critical breakdown voltage,maximal reduction is 130% at the distance of 95 mm. Values of point A are increasing along with larger burning loss angles. Compared with non-burning loss, the value is 7.7 times higher in θ=80° when separation of contact is 17 mm.
Keywords :
circuit breakers; electric breakdown; electric fields; mathematical analysis; SF6 circuit breaker; capacitive current; contact burning loss; dielectric recovery; electric field distortion; electric field distributions; electric field mathematical models; gas breakdown; size 17 mm; size 95 mm; static arc contact; streamer theory; voltage 126 kV; Circuit breakers; Dielectric losses; Electric breakdown; Electric fields; Mathematical model; Sulfur hexafluoride; SF6 circuit breaker; contact burning loss; dielectric recovery characteristic;
Conference_Titel :
Electric Power Equipment - Switching Technology (ICEPE-ST), 2013 2nd International Conference on
Conference_Location :
Matsue
DOI :