• DocumentCode
    1976582
  • Title

    University research approach to switchgear technology//// circuit switching phenomena

  • Author

    Haginomori, Eiichi ; Ikeda, Hinata

  • Author_Institution
    Univ. of Tokyo, Tokyo, Japan
  • fYear
    2013
  • fDate
    20-23 Oct. 2013
  • Firstpage
    1
  • Lastpage
    4
  • Abstract
    The calculation of transient recovery voltage (TRV) was investigated. The current injection principle was used to simplify the calculation. The source side impedance and ramped injection current gives the TRV. The TRV is expressed by the 4 parameter in the standard. The standard TRV is modified by switching circuit conditions. The synthetic short-circuit testing needs to know the TRV modification beforehand. The Laplace transformation is applied to express the 4 parameter TRV by segmenting the straight line. It was shown that the TRV modification by an arrester can be calculated easily by the proposed method.
  • Keywords
    Laplace transforms; arresters; switchgear testing; Laplace transformation; TRV calculation; arrester; current injection principle; ramped injection current; source side impedance; switchgear technology; switching circuit condition; synthetic short-circuit testing; transient recovery voltage calculation; university research; Arresters; Circuit breakers; Educational institutions; Impedance; Switching circuits; Testing; Transient analysis;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electric Power Equipment - Switching Technology (ICEPE-ST), 2013 2nd International Conference on
  • Conference_Location
    Matsue
  • Type

    conf

  • DOI
    10.1109/ICEPE-ST.2013.6804357
  • Filename
    6804357