• DocumentCode
    1984497
  • Title

    A new method of detecting current transducer saturation based on wavelet transform

  • Author

    Guicun, Li ; Wanshun, Liu ; Qingquan, Jia ; Lin, Teng ; Fengmei, Cao ; Ying, Li

  • Author_Institution
    Sifang Inst. North China Electr. Power Univ., Beijing, China
  • Volume
    1
  • fYear
    2001
  • fDate
    15-19 July 2001
  • Firstpage
    617
  • Abstract
    Bus bar differential protection using instantaneous current values is easily influenced by current transducer (CT) saturation, causing maloperation. A method of analyzing the voltage of busbars using the wavelet transform is presented in this paper to detect fault points accurately. One can distinguish whether the CT is saturated based on the time difference between the time of the fault and the time of differential current.
  • Keywords
    busbars; electric current measurement; power system measurement; transducers; wavelet transforms; busbar differential protection; current transducer saturation detection; fault point detection; power system; wavelet transform; Circuit faults; Fault currents; Fault detection; Fourier transforms; Power system protection; Signal analysis; Signal processing; Transducers; Wavelet analysis; Wavelet transforms;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Engineering Society Summer Meeting, 2001
  • Conference_Location
    Vancouver, BC, Canada
  • Print_ISBN
    0-7803-7173-9
  • Type

    conf

  • DOI
    10.1109/PESS.2001.970109
  • Filename
    970109