  • Title

    Detection of insulation faults on disc-type winding transformers by means of leakage flux analysis

  • Author

    Cabanas, M.F. ; Melero, M.G. ; Rojas, C.H. ; Orcajo, G.A. ; Cano, J.M. ; González, F. Pedrayes ; Norniella, J.G. ; Rozada, S. Díaz

  • Author_Institution
    Electr. Eng. Dept., Univ. of Oviedo, Gijon, Spain
  • fYear
    2009
  • fDate
    Aug. 31 20096-Sept. 3 2009
  • Firstpage
    1
  • Lastpage
    6
  • Abstract
    Power transformers figure amongst the most costly pieces of equipment used in electrical systems. Major research effort has therefore focused on detecting failures of their insulating systems prior to unexpected machine outage. Although several industrial methods exist for the on-line and off-line monitoring of power transformers, all of them are expensive and complex, and require the use of specific electronic instrumentation. For these reasons, this paper will present on-line analysis of transformer leakage flux as an efficient alternative procedure for assessing machine integrity and detecting the presence of insulating failures during their earliest stages. A 12kVA 400V/400V power transformer was specifically manufactured for the study. A finite element model of the machine was designed to obtain the transient distribution of leakage flux lines in the machine´s transversal section under normal operating conditions and when shorted turns are intentionally produced. Very cheap, simple sensors, based on air core coils, were built in order to measure the leakage flux of the transformer, and non-destructive tests were also applied to the machine in order to analyse pre- and post-failure voltages induced in the coils. Results point to the ability to detect very early stages of failure, as well as of locating the position of the shorted turn in the transformer windings.
  • Keywords
    fault diagnosis; finite element analysis; fluxmeters; insulation testing; magnetic field measurement; magnetic leakage; nondestructive testing; power transformer insulation; power transformer testing; transformer windings; air core coils; apparent power 12 kVA; disc-type winding transformer; finite element model; insulation fault detection; leakage flux on-line analysis; nondestructive testing; power transformer; voltage 400 V; Coils; Condition monitoring; Electrical equipment industry; Electrical fault detection; Electronics industry; Fault detection; Industrial electronics; Leak detection; Power transformer insulation; Power transformers; Power transformers insulation; diagnosis; finite element method; leakage flux analysis;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Diagnostics for Electric Machines, Power Electronics and Drives, 2009. SDEMPED 2009. IEEE International Symposium on
  • Conference_Location
    Cargese
  • Print_ISBN
    978-1-4244-3441-1
  • Type

    conf

  • DOI
    10.1109/DEMPED.2009.5292756
  • Filename
    5292756