DocumentCode :
1988851
Title :
A frequency response technique to allocate FACTS devices
Author :
Ramirez, Juan M. ; Coronado, Ixtlahuatl
Author_Institution :
CINVESTAV-UNIDAD, Guadalajara, Mexico
Volume :
3
fYear :
2001
fDate :
15-19 July 2001
Firstpage :
1530
Abstract :
In this paper a technique based on open and closed-loop frequency response is proposed to allocate FACTS devices. On those devices with more than one control input, the best one can be selected in order to get the major damping over specific electromechanical modes. The technique is exemplified on a 46-machine power system and a comparison is made with a method based on residues, obtaining similar results.
Keywords :
damping; flexible AC transmission systems; frequency response; load flow control; power system control; power system stability; thyristor applications; 46-machine power system; FACTS devices allocation; TCSC damping controller; UPFC; closed-loop frequency response; control input; damping; electromechanical modes; power system control; power system stability; Control systems; Controllability; Costs; Damping; Frequency response; Power system control; Power system stability; Power system transients; Power systems; Voltage control;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power Engineering Society Summer Meeting, 2001
Conference_Location :
Vancouver, BC, Canada
Print_ISBN :
0-7803-7173-9
Type :
conf
DOI :
10.1109/PESS.2001.970304
Filename :
970304
Link To Document :
بازگشت