    Fault line selection for single-phase earthed fault based on injected active component

  • Author

    Zhang, Ying ; Zhang, Huifen

  • Author_Institution
    Sch. of Control Sci. & Eng., Univ. of Jinan, Jinan, China
  • fYear
    2011
  • fDate
    16-18 Sept. 2011
  • Firstpage
    5270
  • Lastpage
    5273
  • Abstract
    Concerning the current situation of fault line selection of single phase earthed fault in small-current grounded system,plus with analysis of the advantage and disadvantage of currently used in line selection techniques,a method which makes use of neutral point resistant to discriminate the fault line and the normal line during the single-phase earthed fault is proposed in this paper. When the single-phase earthed fault happens, a resistance will be connected at the neutral point in order to provide the post-fault system with zero sequence current´s active component ,which is considered as the criterion for fault line selection.At the last part of this paper the system is modeled by simulation software PSCAD,and the simulation result shows this method works effectively and improve the accuracy of the line selection.
  • Keywords
    earthing; fault diagnosis; power system faults; PSCAD simulation software; fault line selection; injected active component; neutral point resistant; post-fault system; single-phase earthed fault; small-current grounded system; zero sequence current active component; Educational institutions; Fault currents; Industries; PSCAD; Resistance; Water resources; PSCAD simulation; active component of zero-sequence current; non-effective earthed power system; single-phase earthed fault;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical and Control Engineering (ICECE), 2011 International Conference on
  • Conference_Location
    Yichang
  • Print_ISBN
    978-1-4244-8162-0
  • Type

    conf

  • DOI
    10.1109/ICECENG.2011.6057841
  • Filename
    6057841