Title :
Distribution Network Fault Location Algorithm Based on Zero-Sequence Current Phase
Author :
Qi Yulin ; Wen Zhengyang ; Jia Huibin
Author_Institution :
Sch. of Electron. & Commun. Eng., North China Electr. Power Univ., Baoding, China
Abstract :
Based on the theory of the zero-sequence current phase´s fault location method, this article proposes a location algorithm by comparing the relationship between the time and phase radian. The implementation of this method is to use GPS(Global Positioning System) second pulse for synchronous sampling by extracting zero-sequence current, then transmit the collected phase information by the wireless communication module, and confirm the fault interval by the central station software ultimately. Considering the distribution network´s branch line may result in wrong fault location, we put forward the corresponding solution. Finally, I make the analogue simulation aimed at variety of situations of distribution network´s single-phase ground fault by using the simulation module of MATLAB. And I verify the fault location method is feasible by observing phase waveforms of the zero-sequence current in every outgoing line.
Keywords :
Global Positioning System; power distribution faults; GPS second pulse; Global Positioning System second pulse; Matlab; analogue simulation; central station software; distribution network branch line; distribution network fault location algorithm; distribution network single-phase ground fault; fault interval; phase information; wireless communication module; zero-sequence current extraction; zero-sequence current phase fault location method; Circuit faults; Fault location; Global Positioning System; MATLAB; Monitoring; Power systems; Wireless communication;
Conference_Titel :
Engineering and Technology (S-CET), 2012 Spring Congress on
Conference_Location :
Xian
Print_ISBN :
978-1-4577-1965-3
DOI :
10.1109/SCET.2012.6341996