Abstract
This paper proposes diagnosis method and fault-tolerant control algorithm for a grid-connected T-type three-level inverter system. The faulty switch is identified by a normalized average phase current and a change of neutral-point voltage by injection of a negative reactive current. The fault-tolerant algorithm can be applied when the middle switches are faulty by simply modifying the conventional SVM method. The proposed methods are not require additional hardware and do not involve complex calculations. Therefore, the proposed methods are cost-effective and easy to use. The simulation results confirm the feasibility and effectiveness of the proposed fault diagnosis and fault-tolerant methods.
Keywords
fault diagnosis; fault tolerance; invertors; switches; SVM method; fault diagnosis method; fault-tolerant strategy; grid-connected T-type three-level inverter system; negative reactive current; neutral-point voltage; normalized average phase current; open-switch fault detection method; Capacitors; Circuit faults; Fault tolerance; Fault tolerant systems; Inverters; Switches; Vectors;
fLanguage
English
Publisher
ieee
Conference_Titel
Energy Conversion Congress and Exposition (ECCE), 2012 IEEE
Conference_Location
Raleigh, NC
Print_ISBN
978-1-4673-0802-1
Electronic_ISBN
978-1-4673-0801-4
Type
conf
DOI
10.1109/ECCE.2012.6342254
Filename
6342254
Link To Document