DocumentCode
1998576
Title
The research of arc-proofness of set tools for 110-220 kV live line works
Author
Kolker, D.
fYear
1993
fDate
12-17 Sep 1993
Firstpage
387
Lastpage
391
Abstract
This paper presents the results of studies on the arc-proofness of insulating booms of aerial platforms for live line works. The data obtained with 5-20 kA power arcs applied for 1.5-0.1 sec, show acceptable arc-proofness of tested insulating boom samples and full-scale models as well as their ability to withstand nominal voltage or even switching overvoltages after such an arc, if autoreclosing occurs during live line work. The obtained results make possible further improvements of existing telescopic platforms
Keywords
Conductors; Copper; Dielectrics and electrical insulation; Glass; Insulator testing; Power system modeling; Protection; Surges; System testing; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Transmission and Distribution Construction and Live Line Maintenance, 1993. Proceedings from ESMO-93., Sixth International Conference on
Conference_Location
Las Vegas, NV
Print_ISBN
0-7803-1340-2
Type
conf
DOI
10.1109/TDCLLM.1993.316234
Filename
316234