DocumentCode :
2002475
Title :
S-Transform based technique to detect high resistance symmetrical fault during power swing
Author :
Mohamad, Nor Zulaily ; Abidin, Ahmad Farid
Author_Institution :
Fac. of Electr. Eng., Univ. Teknol. MARA, Shah Alam, Malaysia
fYear :
2012
fDate :
23-25 March 2012
Firstpage :
282
Lastpage :
286
Abstract :
Distance relay is designed to operate when fault occurs in the system, but still should block the operation when power swing occurs in the system. However, this blocking scheme prove to vulnerable to distance relay operation as it could block the trip signals when a genuine fault occurs in the system during power swing. Hence, it is desired to develop the proper fault detection technique during power swing to avoid such circumstances. This paper presents S-Transform based detection technique to detect symmetrical fault with high resistance up to 200 Ω during power swing. The proposed scheme is based on S-Transform analysis on the current and voltage waveforms. The effectiveness of the proposed scheme was verified with the IEEE 14 bus test system and simulations results show that the proposed technique can detect high resistance symmetrical fault occurring during power swing from 5 Ω up to 200 Ω.
Keywords :
fault diagnosis; power system faults; power system relaying; transforms; IEEE 14 bus test system; S-transform analysis; S-transform based detection; blocking scheme; distance relay; fault detection; high resistance symmetrical fault; power swing; Feature extraction; Impedance; Power system stability; Protective relaying; Resistance; Voltage measurement; S-Transform; distance protection; power swing; symmetrical fault;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Signal Processing and its Applications (CSPA), 2012 IEEE 8th International Colloquium on
Conference_Location :
Melaka
Print_ISBN :
978-1-4673-0960-8
Type :
conf
DOI :
10.1109/CSPA.2012.6194734
Filename :
6194734