    Influence of ring-main-units and substations on the propagation of PD pulses

  • Author

    Wouters, Peter ; Wagenaars, Paul ; Van der Wielen, Peter ; Steennis, Fred

  • Author_Institution
    Fac. of Electr. Eng., Eindhoven Univ. of Technol., Eindhoven, Netherlands
  • fYear
    2010
  • fDate
    4-9 July 2010
  • Firstpage
    1
  • Lastpage
    4
  • Abstract
    Partial discharge (PD) location in online diagnostics on medium voltage cables is achieved using a sensor at each cable end. Monitoring consecutive cables with a single monitoring system would, however, be more efficient. Moreover, substations and ring main units (RMU) along a cable connection without possibilities for sensor installation can be circumvented by installing the sensor at the next RMU. This paper studies the influence of RMUs and substations along the cable under test on online PD monitoring, including their influence on detection sensitivity, location accuracy and charge estimate accuracy. Models for RMUs and substation are proposed and verified by measurements. The performance of online PD monitoring is studied for a number of network configurations.
  • Keywords
    partial discharge measurement; power cables; power system measurement; substations; cable under test; medium voltage cables; online diagnostics; partial discharge location; partial discharge pulse propagation; ring main units; sensor installation; substations; Accuracy; Impedance; Matched filters; Monitoring; Partial discharges; Substations; Transfer functions; defect location; partial discharges; power cables; ring-main-units; substations;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Solid Dielectrics (ICSD), 2010 10th IEEE International Conference on
  • Conference_Location
    Potsdam
  • Print_ISBN
    978-1-4244-7945-0
  • Electronic_ISBN
    978-1-4244-7943-6
  • Type

    conf

  • DOI
    10.1109/ICSD.2010.5568092
  • Filename
    5568092