Study on installing small reactance in neutral point of 500kV transformer on Guangdong power grid
Author :
Cao, Huazhen ; Cai, Guanglin ; Shi, Hui ; Zhang, Yongjun
Author_Institution :
Guangdong Power Grid Corp., Guangzhou, China
fYear :
2011
fDate :
16-18 Sept. 2011
Firstpage :
2594
Lastpage :
2597
Abstract :
With the 500kV substations put into operation one after the other, the capacity and scale of 500kV autotransformer are more and more large. The single-phase short-circuit current at 220 kV buses of 500kV substations is higher than three-phase, the safe operation can´t be satisfied. It can be controlled by adding small reactance at 500kV autotransformers from the operation experience of all over the world. This paper analyzes the reason and necessity for adding small reactance at 500kV autotransformers from the level of short current on Guangdong, and studies the types of substations which are fit to installing them. It also studies the effect of the small reactance capacity on limiting short-circuit current of single phase, and proposes the installation program for Guangdong power grid.
Keywords :
power grids; power transformers; short-circuit currents; substations; Guangdong power grid; autotransformer; neutral point; single-phase short-circuit current; small reactance installation; substations; voltage 220 kV; voltage 500 kV; Limiting; Power grids; Power supplies; Power transformer insulation; Resistance; Substations; Voltage measurement; neutral point; power grid; short-circuit current; small reactance;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical and Control Engineering (ICECE), 2011 International Conference on
Conference_Location :
Yichang
Print_ISBN :
978-1-4244-8162-0
Type :
conf
DOI :
10.1109/ICECENG.2011.6058464
Filename :
6058464
Link To Document :
بازگشت