Title :
Effect of A-Spot Temperature on the Temperature of External Surfaces in an Electrical Connection
Author :
Wilson, Campbell ; McIntosh, G. ; Timsit, Roland S.
Author_Institution :
Design Resource Group, Richmond Hill, ON, Canada
Abstract :
Infrared thermography is widely used to monitor the health of electrical power connections in live electrical lines. Although thermal imaging is helpful in locating faulty connections, surface temperature measurement alone is a poor indicator for fault severity assessment. Furthermore, under low load or other adverse environmental situations, the technique may not provide sufficient information to identify electrical connections in the initial or even advanced phases of electrical failure. This limitation stems from the large difference between the temperature of overheated electrical contact spots in a failing electrical interface and the temperature of the external surfaces of the electrical joint. This paper reports the results of calculations, based on a simple computer model, that illustrate the differences between the temperature of an electrical interface and the external surface temperature of the connection.
Keywords :
electric connectors; electrical contacts; failure analysis; infrared imaging; a-spot temperature effect; computer model; electrical failure; electrical interface; electrical joint; electrical lines; electrical power connections; external surface temperature; fault severity assessment; infrared thermography; overheated electrical contact spots; surface temperature measurement; thermal imaging; Bridge circuits; Bridges; Conductors; Contacts; Copper; Heat transfer; Temperature distribution;
Conference_Titel :
Holm Conference on Electrical Contacts (HOLM) , 2013 IEEE 59th
Conference_Location :
Newport, RI
Print_ISBN :
978-1-4799-1556-9
DOI :
10.1109/HOLM.2013.6651407