• DocumentCode
    2007055
  • Title

    Discharges in AC-stressed oil gaps

  • Author

    Lundgaard, Lars E.

  • Author_Institution
    Norwegian Electr. Power Res. Inst., Trondheim, Norway
  • fYear
    1993
  • fDate
    19-23 Jul 1993
  • Firstpage
    337
  • Lastpage
    341
  • Abstract
    Rates and phase distribution of discharges in transformer oil in an AC-stressed point-plane gap have been measured using a phase-synchronized multichannel analyzer. Three types of discharges were observed: negative discharges, which occurred at a high rate, and small and large positive discharges, which occurred at lower rates. The large positive discharges resulted in breakdown of the oil gaps. The discharge rates increased with reduced tip curvature and increasing voltage. The discharge activity was found to vary stochastically with time, and the total occurrence rate varied from 0.007 to 25 Hz. The discharges appeared over a wide phase window around the peak voltage
  • Keywords
    transformer oil; 0.007 to 25 Hz; AC-stressed oil gaps; AC-stressed point-plane gap; breakdown; discharge activity; discharge rates; discharges; negative discharges; peak voltage; phase distribution; phase-synchronized multichannel analyzer; positive discharges; tip curvature; transformer oil; Detectors; Dielectric liquids; Electric breakdown; Electrodes; Oil insulation; Petroleum; Power transformer insulation; Pulse circuits; Stress; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Conduction and Breakdown in Dielectric Liquids,1993., ICDL '93., IEEE 11th International Conference on
  • Conference_Location
    Baden-Dattwil
  • Print_ISBN
    0-7803-0791-7
  • Type

    conf

  • DOI
    10.1109/ICDL.1993.593963
  • Filename
    593963