• DocumentCode
    2007785
  • Title

    Electrical charges generated by a flow of oil in power transformers

  • Author

    Touchard, G. ; Grimaud, P.O. ; Romat, H. ; Moreau, O.

  • Author_Institution
    Lab. de Physique et Mecanique des Fluides, CNRS, Poitiers, France
  • fYear
    1993
  • fDate
    19-23 Jul 1993
  • Firstpage
    497
  • Lastpage
    503
  • Abstract
    An attempt has been made to gain a better understanding of the formation of electrical charge appearing within oil circulating inside a rectangular pressboard channel. Experiments confirm that the charge accumulated on the surface of the pressboard does not limit the process of charge generation. It is concluded that the roughness of the surface and its nonhomogeneity are factors that must be taken into account in order to explain the high-energy level of the discharges occurring in power transformers
  • Keywords
    transformer oil; charge generation; discharges; electrical charges; oil flow; power transformers; rectangular pressboard channel; surface roughness; Coatings; Contacts; Ducts; Electrical equipment industry; Geometry; Industrial accidents; Petroleum; Power generation; Power transformers; Space charge;