DocumentCode :
2016563
Title :
A simple Discrete Fourier Transform-based synchronization method for power quality measurement
Author :
Diego, R.I. ; Barros, Joao ; de Apraiz, M. ; Prieto, Josep
Author_Institution :
Dept. Electron. & Comput., Univ. of Cantabria, Santander, Spain
fYear :
2013
fDate :
16-20 June 2013
Firstpage :
1
Lastpage :
6
Abstract :
A simple method for real-time synchronization of power quality measurements in low-voltage supply systems is presented. Proper synchronization between the data acquisition window and the power system frequency is necessary to accurately measure the harmonic distortion. The proposed method is based on the use of the standard Discrete Fourier Transform method using a 10-cycle width rectangular window and a fixed sampling frequency. The algorithm iteratively adjusts the sampling window width in order to reduce the synchronization error due to the spectral leakage produced by the truncation of the signal in the time-domain. Simulated results demonstrate the good performance of the method proposed.
Keywords :
data acquisition; discrete Fourier transforms; harmonic distortion; power supply quality; power system measurement; time-domain analysis; 10-cycle width rectangular window; data acquisition window; discrete Fourier transform-based synchronization method; fixed sampling frequency; harmonic distortion; low-voltage supply systems; power quality measurement; power system frequency; real-time synchronization; synchronization error; time-domain; Discrete Fourier transforms; Frequency measurement; Frequency synchronization; Harmonic analysis; Harmonic distortion; Standards; Synchronization; Synchronization; frequency estimation; non stationary systems; power quality;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
PowerTech (POWERTECH), 2013 IEEE Grenoble
Conference_Location :
Grenoble
Type :
conf
DOI :
10.1109/PTC.2013.6652135
Filename :
6652135
Link To Document :
بازگشت