DocumentCode
2017036
Title
Applying PTP-to-SNTP time-gateway to IEC61850 systems
Author
Ferrari, Paolo ; Flammini, Alessandra ; Rinaldi, Stefano ; Prytz, Gunnar
Author_Institution
Dept. of Inf. Eng., Univ. of Brescia, Brescia, Italy
fYear
2011
fDate
5-9 Sept. 2011
Firstpage
1
Lastpage
4
Abstract
The paper describes the application of an improved Time Gateway for simplifying the integration of old IEC 61850 devices in new IEC 61850 Substation Automation System with IEEE 1588 PTP. Old devices typically retrieve time information with the well-known SNTP protocol which uses very different time representations and synchronization strategies with respect to PTP. Hence, the paper uses a transparent, full-software, Time Gateway for interfacing SNTP devices with a PTP synchronization domain, demonstrating its applicability by means of a prototype based on an FPGA. Experimental results show the Time Gateway improves the overall performance with respect to an SNTP-only system. Moreover, the experiments demonstrate that the synchronization accuracy is limited by the SNTP.
Keywords
IEC standards; IEEE standards; field programmable gate arrays; internetworking; protocols; substation automation; synchronisation; FPGA; IEC 61850 device; IEC 61850 standard; IEEE 1588 PTP; PTP-to-SNTP time-gateway; SNTP protocol; substation automation system; synchronization strategy; time representation strategy; Accuracy; Hardware; Logic gates; Protocols; Software; Substations; Synchronization;
fLanguage
English
Publisher
ieee
Conference_Titel
Emerging Technologies & Factory Automation (ETFA), 2011 IEEE 16th Conference on
Conference_Location
Toulouse
ISSN
1946-0740
Print_ISBN
978-1-4577-0017-0
Electronic_ISBN
1946-0740
Type
conf
DOI
10.1109/ETFA.2011.6059153
Filename
6059153
Link To Document