DocumentCode
2021007
Title
Practical experience of using additional earthing of the faulty phase during a ground fault
Author
Topolanek, David ; Orsagova, J. ; Toman, Petr ; Dvorak, J.
Author_Institution
Fac. of Electr. Eng. & Commun., Brno Univ. of Technol., Brno, Czech Republic
fYear
2013
fDate
16-20 June 2013
Firstpage
1
Lastpage
6
Abstract
The paper is focused on the operational experience with an automatic system for suppression of a fault current during a ground fault by the additional earthing of the faulted phase in a supply substation. Such system was experimentally installed in the Brno-Medlánky 110/22 kV substation. To verify the benefits of the system as well as to assess its possible failings, twenty-four experimental measurements based on a theoretical study were performed. During those experiments, low-resistance and arc ground faults were monitored in the urban and suburban part of the compensated network with a capacitive current of 300 A and 800 A. The results of the crucial experiments and the evaluation of the system functioning are summed up in the final part of the paper.
Keywords
earthing; substation protection; Brno-Medlanky substation; current 300 A; current 800 A; earthing; fault current suppression; ground fault; voltage 110 kV; voltage 22 kV; Circuit faults; Current measurement; Earth; Fault currents; Grounding; Resistance; Substations; capacitive current; compensated; distribution network; earthing; faulty current; ground fault; residual current; shunt;
fLanguage
English
Publisher
ieee
Conference_Titel
PowerTech (POWERTECH), 2013 IEEE Grenoble
Conference_Location
Grenoble
Type
conf
DOI
10.1109/PTC.2013.6652291
Filename
6652291
Link To Document