Higher withstand MCC for better selective coordination
Author :
Kumar, Rajiv ; Reed, Douglas ; Morris, Robert ; Terry, Samuel
Author_Institution :
Eaton Corp., Fayetteville, NC, USA
fYear :
2009
fDate :
14-16 Sept. 2009
Firstpage :
1
Lastpage :
6
Abstract :
Underwriters Laboratories 845 standard for low voltage motor control centers requires a short circuit withstand rating on the bus for only 3 cycles. However, in power distribution systems today low voltage motor control centers are increasingly fed from low voltage low voltage power circuit breakers located in low voltage switchgear ahead of or in a motor control center line up; these low voltage low voltage power circuit breakers are typically rated for up to 30 cycles short delay which can be greater than the UL 845 short circuit withstand test requirements. The trip settings on these low voltage low voltage power circuit breakers may include short-time delay that can result in the motor control center enduring fault currents for much more than the 3 cycles for which it is rated. In this paper it is proposed that motor control center bus designed and tested for higher number of cycles of withstand can address the above potential issue by offering better coordination and safer power distribution design options such as: 1) The instantaneous setting on the upstream low voltage power breaker can be eliminated to provide for increased coordination at the motor control center level. 2) Low voltage low voltage power circuit breakers (or where applicable larger frame molded case circuit breakers with electronic trips) can be used in a motor control center line up both as mains and feeders when increased coordination is required with downstream loads. 3) When selective coordination is required by National Electric Code for motor control centers being used in emergency, legally required standby or health care essential systems, motor control centers with increased withstand ratings can be provided, that are compatible with higher over current protective device short time delay time settings. 4) Better system design flexibility by allowing motor control center assemblies to be integrated in to a 30 cycle rated low voltage switchgear line up.
Keywords :
circuit breakers; fault currents; machine control; standards; voltage control; UL 845 standard; Underwriters Laboratories 845 standard; fault currents; low voltage motor control centers; low voltage power circuit breakers; low voltage switchgear; molded case circuit breakers; over current protective device; power distribution systems; short circuit withstand rating; Circuit breakers; Circuit testing; Delay; Fault currents; Laboratories; Low voltage; Motor drives; Power distribution; Switchgear; System testing; MCC; Withstand ratings; horizontal bus; low voltage power circuit breakers; molded case circuit breakers (MCCB); selective coordination; vertical bus;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Petroleum and Chemical Industry Conference, 2009. PCIC 2009. 2009 Record of Conference Papers - Industry Applications Society 56th Annual
Conference_Location :
Anaheim, CA
ISSN :
0090-3507
Print_ISBN :
978-1-4244-3798-6
Electronic_ISBN :
0090-3507
Type :
conf
DOI :
10.1109/PCICON.2009.5297151
Filename :
5297151
Link To Document :
بازگشت