Abstract :
Various types of numerical protective relays allow the user to specify a custom overcurrent protection characteristic. For most end users this feature is simply a curiosity or completely ignored, an untapped capability of the device. Other users apply a custom curve shape in isolated cases to solve difficult coordination problems. This is rather unfortunate because the precise tripping control that can be obtained from a user-defined custom curve offers many advantages over traditional inverse curve shapes. Some of these benefits include increased safety to personnel, improved equipment protection, better handling of impact loads, and enhanced selectivity at bolted and arcing fault current levels. This paper provides specific power system examples that demonstrate the benefits of replacing electromechanical relay replications in favor of custom curve shaping obtained from numerical relays in applications starting from the incoming substation down to the unit substations and motor controllers. These samples will show how the user can specify tripping characteristics to reduce the available arc-flash energy to protect workers and equipment. They will illustrate how sudden increased loading can be accommodated to allow for a load shedding system to operate. The paper will also offer lessons learned and suggestions for future development of this custom programming feature of numerical relays.
Keywords :
electrical safety; load shedding; overcurrent protection; personnel; relay protection; substation protection; arcing fault current level; custom overcurrent relay characteristics; equipment protection; load shedding system; motor controllers; numerical protective relays; numerical relays; overcurrent protection characteristics; personnel safety; substation; tripping control; user-defined custom curve; Fault currents; Personnel; Power system faults; Power system protection; Power system relaying; Protective relaying; Relays; Safety devices; Shape control; Substation protection; Overcurrent protection; arc flash; coordination; custom curves; impact loading; numerical relays; safety by design;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Petroleum and Chemical Industry Conference, 2009. PCIC 2009. 2009 Record of Conference Papers - Industry Applications Society 56th Annual
Conference_Location :
Anaheim, CA
ISSN :
0090-3507
Print_ISBN :
978-1-4244-3798-6
Electronic_ISBN :
0090-3507
Type :
conf
DOI :
10.1109/PCICON.2009.5297155
Filename :
5297155
Link To Document :
بازگشت