DocumentCode :
2031230
Title :
Reducing arc flash risk with the application of protective relays
Author :
Luna, Ray ; Cassidy, Brian ; Franco, Jesus
Author_Institution :
GE Multilin, League City, TX, USA
fYear :
2009
fDate :
14-16 Sept. 2009
Firstpage :
1
Lastpage :
9
Abstract :
The exposure to an arc flash high incident energy fault to technicians operating low and medium voltage switching equipment is a daily hazard in the workplace and there is an opportunity to improve safety. While PPE protects for first and second degrees burns it could not provide sufficient protection for the impact and forces that a high incident energy arcing fault produces and the gases released for exposures over 40 cal/cm2. One solution is to reduce the incident energy of the arcing fault below 40 cal/cm2, This paper analyzes methods to reduce the exposure of personnel to high-energy arcing faults to levels below 40 cal/cm2, and also defines a method to determine the limits of coordination among protective devices to identify where the selectivity could be jeopardized.
Keywords :
arcs (electric); electrical faults; electrical safety; relay protection; arc flash risk reduction; arcing fault; energy fault; incident energy; protective device; protective relay; Circuit faults; Communication system control; Fault detection; Gases; Hazards; Low voltage; Materials testing; Personnel; Protection; Protective relaying; Arc flash; arc flash hazards; coordination; fault studies;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Petroleum and Chemical Industry Conference, 2009. PCIC 2009. 2009 Record of Conference Papers - Industry Applications Society 56th Annual
Conference_Location :
Anaheim, CA
ISSN :
0090-3507
Print_ISBN :
978-1-4244-3798-6
Electronic_ISBN :
0090-3507
Type :
conf
DOI :
10.1109/PCICON.2009.5297175
Filename :
5297175
Link To Document :
بازگشت