Abstract :
This paper analyzes the motor bus transfer (MBT) issue and developing schemes to accomplish transfer that promote process continuity while causing no damage to the motors or the loads. An important value to decide the viability of MBT is the resultant volts per hertz (V/Hz). The resultant V/Hz issue is exacerbated when the phase angle difference increases and the voltage difference increases. Several methods have been proposed and discussed here
Keywords :
electric motors; machine testing; machine theory; high-speed motor bus transfer; industrial facility; phase angle difference; power plant; resultant volts per hertz; voltage difference; Aggregates; Couplings; Equations; Frequency; Induction motors; Industrial plants; Storms; Synchronous motors; Torque; Voltage;