• DocumentCode
    2031699
  • Title

    Standard CT accuracy ratings in metal-clad switchgear

  • Author

    Zocholl, S.E.

  • Author_Institution
    Schweitzer Eng. Lab. Inc., USA
  • fYear
    2006
  • fDate
    4-6 April 2006
  • Abstract
    This paper shows the consequences of low accuracy ratings and analyzes the relay response for fault currents in the range of 25 kA to 50 kA, using the CT accuracy rating from the relay data acquisition. To ensure proper relaying performance, the user should make a careful analysis of CT performance considering the relaying requirements for the specific short circuit current and the secondary circuit impedances. The careful analysis of CT performance for high magnitude offset fault requires computer simulation of the relay, as well as the CT, and cannot be carried out by manual calculation.
  • Keywords
    current transformers; data acquisition; digital simulation; relay protection; short-circuit currents; switchgear; CT accuracy; computer simulation; data acquisition; fault current; metal-clad switchgear; relaying performance; secondary circuit impedance; short circuit current; Circuit faults; Current measurement; Current transformers; Data acquisition; Digital filters; Digital relays; Fault currents; Protection; Protective relaying; Switchgear;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Protective Relay Engineers, 2006. 59th Annual Conference for
  • Print_ISBN
    1-4244-0043-0
  • Type

    conf

  • DOI
    10.1109/CPRE.2006.1638702
  • Filename