DocumentCode :
2032417
Title :
Frequency response analysis approach for condition monitoring of transformer
Author :
Nirgude, Pradeep M. ; Gunasekaran, B. ; Channakeshava ; Rajkumar, A.D. ; Singh, B.P.
Author_Institution :
Central Power Res. Inst., Hyderabad, India
fYear :
2004
fDate :
17-20 Oct. 2004
Firstpage :
186
Lastpage :
189
Abstract :
The paper deals with the frequency response analysis (FRA) technique, which uses sweep frequency responses of the transformer winding to study the various aspects of winding deformations. Experimental and theoretical investigations were carried out on the HV disc winding of a 11 kV/433 V, 1 MVA transformer. Sweep frequency responses of this transformer were obtained experimentally. Theoretical computations of frequency responses using EMTP are made by representing the transformer winding as ladder network parameters, comprising inductances and capacitances that are computed from its design data. The paper presents the theoretical and experimental results and analysis of the frequency responses on the variations of the winding parameters, which represents the winding deformation.
Keywords :
EMTP; capacitance; condition monitoring; deformation; frequency response; inductance; ladder networks; power system measurement; power transformers; transformer windings; 1 MVA; 11 kV; 433 V; EMTP; HV disc winding; capacitances; frequency response analysis; high voltage power transformers; inductances; ladder network parameters; transformer condition monitoring; transformer winding sweep frequency response; winding deformations; Capacitance; Condition monitoring; Frequency response; Instruments; Oil insulation; Power transformer insulation; Power transformers; Testing; US Department of Transportation; Windings;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Insulation and Dielectric Phenomena, 2004. CEIDP '04. 2004 Annual Report Conference on
Print_ISBN :
0-7803-8584-5
Type :
conf
DOI :
10.1109/CEIDP.2004.1364220
Filename :
1364220
Link To Document :