• DocumentCode
    2032560
  • Title

    Couplers for on-line time domain reflectometry diagnostics of power cables

  • Author

    Dubickas, V. ; Edin, H.

  • Author_Institution
    Dept. of Electr. Eng., R. Inst. of Technol., Stockholm, Sweden
  • fYear
    2004
  • fDate
    17-20 Oct. 2004
  • Firstpage
    210
  • Lastpage
    214
  • Abstract
    This paper investigates three types of couplers for sending and receiving a time domain reflectometry (TDR) signal to and from a cable, on-line. Transfer functions of the couplers were estimated and lumped element models were built. The couplers were placed on a power cable with high voltage (HV) terminations. Measurements were performed at a HV, simulating realistic conditions. In this cable, we investigated voltage pulse injection, propagation, and detection for different coupler topologies and HV terminations.
  • Keywords
    electric connectors; lumped parameter networks; power cable insulation; power cable testing; time-domain reflectometry; transfer functions; HV terminations; TDR on-line couplers; coupler topology; coupler transfer functions; high voltage power cable; lumped element models; power cable diagnostics; power cable insulation diagnostics; pulse detection; pulse propagation; time domain reflectometry; voltage pulse injection; Couplers; Frequency measurement; Magnetic field measurement; Power cables; Pulse measurements; Reflectometry; Time measurement; Transfer functions; Voltage; Wires;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation and Dielectric Phenomena, 2004. CEIDP '04. 2004 Annual Report Conference on
  • Print_ISBN
    0-7803-8584-5
  • Type

    conf

  • DOI
    10.1109/CEIDP.2004.1364226
  • Filename
    1364226