• DocumentCode
    2033843
  • Title

    The influence of winding type on the recognition of partial discharges [power transformer testing]

  • Author

    Jayalalitha, S. ; Palani, A. ; Jayashankar, V.

  • Author_Institution
    Indian Inst. of Technol. Madras, Chennai, India
  • fYear
    2004
  • fDate
    17-20 Oct. 2004
  • Firstpage
    446
  • Lastpage
    449
  • Abstract
    An instrumentation scheme is proposed for the acquisition of waveforms during the lightning impulse test on transformers. Three filters segregate the response into distinct frequency bands. As partial discharge signals primarily influence the high frequency behaviour, experiments are reported on disc, interleaved disc and layer windings.
  • Keywords
    band-pass filters; high-pass filters; impulse testing; low-pass filters; partial discharge measurement; power transformer insulation; power transformer testing; transformer windings; SISO system; bandpass filter; disc windings; highpass filter; interleaved disc windings; layer windings; lightning impulse test; lowpass filter; partial discharge recognition; power transformer testing; transformer winding type; triple filter method; Band pass filters; Frequency; Impulse testing; Instruments; Lightning; Low pass filters; Partial discharges; Resistors; Switches; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation and Dielectric Phenomena, 2004. CEIDP '04. 2004 Annual Report Conference on
  • Print_ISBN
    0-7803-8584-5
  • Type

    conf

  • DOI
    10.1109/CEIDP.2004.1364283
  • Filename
    1364283