Title :
Partial discharge detection and localization in power transformers
Author_Institution :
Schering-Inst., Univ. of Hannover, Germany
Abstract :
An enhanced partial discharge (PD) measurement and evaluation techniques used for an improved condition assessment on power transformers are introduced and discussed. The PD measurement system itself is based on a wide-band electrical decoupling of the PD signals using special sensors, a superior signal transmission technology and the transfer function, thus the PD can be detected, localized and furthermore the influences of disturbing noise be significantly reduced during the online measurement. Remaining noises and pulses from outside the transformer are afterwards suppressed using improved digital signal processing tools. The measurements in the laboratory and on-site show reasonable results and the PD measuring system can be integrated as a component in a comprehensive monitoring and diagnostic system.
Keywords :
condition monitoring; partial discharge measurement; power transformers; transfer functions; PD detection; PD localization; PD signal electrical decoupling; diagnostic system; digital signal processing; monitoring system; noise suppression; on-site measurements; online measurement noise reduction; partial discharge measurement; power transformer condition assessment; transfer function; Electric variables measurement; Noise measurement; Noise reduction; Partial discharge measurement; Partial discharges; Power measurement; Power transformers; Sensor systems; Transfer functions; Wideband;
Conference_Titel :
Electrical Insulation and Dielectric Phenomena, 2004. CEIDP '04. 2004 Annual Report Conference on
Print_ISBN :
0-7803-8584-5
DOI :
10.1109/CEIDP.2004.1364288