    Separation distances for air termination systems in proximity to large conductive areas

  • Author

    Zischank, W. ; Stimper, K.

  • Author_Institution
    Inst. of High Voltage Tech. & Lighting Res., Univ. of the Fed. Armed Forces Munich, Neubiberg, Germany
  • fYear
    2012
  • fDate
    2-7 Sept. 2012
  • Firstpage
    1
  • Lastpage
    6
  • Abstract
    In case of a direct lightning strike to a building dangerous sparking may occur between the external lightning protection system and conductive parts inside or at the building. To avoid such side flashes a minimum separation distance between these parts has to be kept. The standard IEC 62305-3 provides an equation and parameters to determine the necessary separation distance. The parameters given there were developed for large loops, many meters wide. Nowadays, it often occurs that the air termination system is to be placed relatively close to large conductive areas. Typical examples are air termination wires placed on a metal roof or on a reinforced concrete structure. For such cases, it has to be expected that the parameters are different to those given in IEC 62305-3. Objective of this paper is to experimentally determine these parameters.
  • Keywords
    IEC standards; lightning protection; air termination systems; air termination wires; building; direct lightning strike; external lightning protection system; metal roof; reinforced concrete structure; separation distances; side flashes; standard IEC 62305-3; Dielectric breakdown; IEC standards; Inductance; Metals; Voltage measurement; Wires; Lightning; Separation distance;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Lightning Protection (ICLP), 2012 International Conference on
  • Conference_Location
    Vienna
  • Print_ISBN
    978-1-4673-1898-3
  • Electronic_ISBN
    978-1-4673-1896-9
  • Type

    conf

  • DOI
    10.1109/ICLP.2012.6344408
  • Filename
    6344408