Separation distances for air termination systems in proximity to large conductive areas
Author
Zischank, W. ; Stimper, K.
Author_Institution
Inst. of High Voltage Tech. & Lighting Res., Univ. of the Fed. Armed Forces Munich, Neubiberg, Germany
fYear
2012
fDate
2-7 Sept. 2012
Firstpage
1
Lastpage
6
Abstract
In case of a direct lightning strike to a building dangerous sparking may occur between the external lightning protection system and conductive parts inside or at the building. To avoid such side flashes a minimum separation distance between these parts has to be kept. The standard IEC 62305-3 provides an equation and parameters to determine the necessary separation distance. The parameters given there were developed for large loops, many meters wide. Nowadays, it often occurs that the air termination system is to be placed relatively close to large conductive areas. Typical examples are air termination wires placed on a metal roof or on a reinforced concrete structure. For such cases, it has to be expected that the parameters are different to those given in IEC 62305-3. Objective of this paper is to experimentally determine these parameters.
Keywords
IEC standards; lightning protection; air termination systems; air termination wires; building; direct lightning strike; external lightning protection system; metal roof; reinforced concrete structure; separation distances; side flashes; standard IEC 62305-3; Dielectric breakdown; IEC standards; Inductance; Metals; Voltage measurement; Wires; Lightning; Separation distance;
fLanguage
English
Publisher
ieee
Conference_Titel
Lightning Protection (ICLP), 2012 International Conference on
Conference_Location
Vienna
Print_ISBN
978-1-4673-1898-3
Electronic_ISBN
978-1-4673-1896-9
Type
conf
DOI
10.1109/ICLP.2012.6344408
Filename
6344408
Link To Document