DocumentCode :
2035195
Title :
Study on the electrical strength of distribution insulators under steep front, short duration pulse
Author :
Grzybowski, S. ; Song, Y. ; Kappenman, J.
Author_Institution :
Mississippi State Univ., MS, USA
fYear :
2004
fDate :
17-20 Oct. 2004
Firstpage :
643
Lastpage :
646
Abstract :
To compare the insulation characters of different distribution insulators under steep front short duration (SFSD) pulses, SFSD pulses are generated and applied on 5 selected kinds of typical 15 kV insulators. The generated SFSD impulse in this study has a 60 ns front and less than 200 ns tail. In order to measure the critical flashover (CFO) voltage under SFSD pulses, an up and down method, as in lightning impulses, is developed and used. The CFO voltage and V-t characteristics for all 5 kinds of 15 kV insulators are evaluated under dry and wet conditions with both negative and positive polarity impulses. In order to study the added insulation strength by a wood crossarm and to compare the results, all the above-mentioned tests are performed again with the 15 kV distribution insulator plus a 0.5 foot and later 1 foot wood crossarm.
Keywords :
electric strength; flashover; impulse testing; insulators; wood; 0.5 ft; 1 ft; 15 kV; 200 ns; 60 ns; CFO voltage; SFSD pulses; critical flashover voltage; distribution insulator electrical strength; dry conditions; impulse polarity; insulation strength; lightning impulses; steep front short duration pulses; up and down method; wet conditions; wood crossarm; Character generation; Dielectrics and electrical insulation; Flashover; Foot; Insulator testing; Lightning; Pulse generation; Pulse measurements; Tail; Voltage;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Insulation and Dielectric Phenomena, 2004. CEIDP '04. 2004 Annual Report Conference on
Print_ISBN :
0-7803-8584-5
Type :
conf
DOI :
10.1109/CEIDP.2004.1364332
Filename :
1364332
Link To Document :
بازگشت